All prices include 18% GST  ·  GST tax invoice on every order

OhmKart

How-to · 4 min read

How to test insulation resistance: motors, cables and panels, step by step

A safe, practical procedure for insulation resistance testing with a digital insulation tester, including voltage selection, temperature correction and how to read PI and DAR.

By the OhmKart team, Cambridge Instruments & Engg. Co. · Updated 20 October 2026

The short answer

Isolate, prove dead, disconnect anything electronic, pick the test voltage from the equipment rating, hold the test for one minute (ten for PI), note the temperature, then discharge before you touch anything. Compare the reading to the minimum for your standard and to the last reading you took.

Safety. Insulation testing applies a dangerous voltage. Only competent people should do it, following the permit and lock-out rules of the site. Never test live equipment.

Before you start

  1. Isolate the equipment and lock it out. Prove it is dead with a voltage tester or multimeter.
  2. Disconnect it from the supply, the VFD or soft starter, surge arrestors, capacitors, electronic meters and any control wiring that could be damaged.
  3. Discharge the equipment to earth, particularly cables and large windings that can hold charge.
  4. Clean and dry the terminal area. Dirt and moisture on terminals give a false low reading.
  5. Check your tester and leads. Look for damaged insulation on the leads and a healthy battery. Briefly test the tester on a known good value if it has a test facility.

Choose the test voltage

EquipmentSuggested test voltageCommon minimum
Control wiring, SELV and PELV circuits250 V0.5 MΩ
LV wiring and equipment up to 500 V500 V1 MΩ
415 V motors, panels, busbars500 V or 1000 V1 MΩ
3.3 kV motors and cables1000 V to 2500 VRated kV plus 1 MΩ
6.6 kV and 11 kV equipment2500 V or 5000 VRated kV plus 1 MΩ

Minimums follow IEC 60364-6 for installations and IEEE 43 for motors and generators. Follow your own site or manufacturer limits if they are stricter.

Testing a motor

  1. Open the terminal box and separate the star or delta links so each winding is independent, if the procedure allows.
  2. Connect the tester's EARTH lead to the motor frame (a bare, clean metal point) and the LINE lead to one winding terminal.
  3. Select the test voltage and press and hold the test button. Read the value at 60 seconds and note it.
  4. Repeat for each winding to earth. If you want to check winding to winding, test one against the others.
  5. For large or HT motors, run the test for 10 minutes and record the reading at 1 minute and 10 minutes for the PI.
  6. Release the test and let the tester discharge the winding. Short the terminals to earth for a few minutes before touching.

Testing a cable

  1. Disconnect both ends and keep the far end clear of any metalwork and people.
  2. For a multicore cable, test each core to earth (armour or screen) with the other cores also connected to earth, then test core to core.
  3. Apply the test voltage for one minute and record the reading. Longer cables have lower resistance because they have more insulation in parallel, so compare like with like.
  4. Discharge each core to earth before reconnecting. HT cable can hold charge for a long time.

Testing a panel or busbar

  1. Isolate the incomer and open all feeder switches so the busbars are clear.
  2. Disconnect electronics, meters and surge protection devices.
  3. Test each phase to earth and each phase to the others, at 500 V or 1000 V.
  4. A low reading often points to dust, damp or tracking on the insulators. Clean, dry and test again.

Reading the result

  • Compare against the minimum for your standard. Anything below it should be investigated before the equipment is put back into service.
  • Compare against the last reading. A steady downward trend over years is an early warning, even if the number is still above the minimum.
  • Temperature matters. Insulation resistance roughly halves for each 10 °C rise, so correct readings to a reference temperature (40 °C is common) or record the temperature with each result.
  • Use PI and DAR when you can. The PI is the 10 minute reading divided by the 1 minute reading; 2 or more is generally healthy. The DAR is the 60 second reading divided by the 30 second one; above about 1.4 is generally good.
How long should I hold the test voltage?

One minute is the standard time for a spot reading. For a polarization index, hold it for ten minutes and record the reading at one minute and at ten minutes.

Why does my reading keep rising during the test?

That is normal. As the insulation polarises, the leakage current falls and the resistance climbs. A reading that rises well indicates healthy insulation. A reading that stays flat or falls suggests moisture or contamination.

Can I test a motor connected to a VFD?

No. Disconnect the motor from the drive first. The test voltage can damage the drive electronics.

What if the reading is below the minimum?

Do not energise the equipment. Dry it out, clean the terminals, and test again. If it stays low, the insulation needs repair or rewinding.

Keep reading